Details
Omniguard Flame and Gas Detector 660-10100
Performance ratings
Responsive to hydrocarbon (gasoline, propane, methane, alcohol, etc.)
and non-hydrocarbon (hydrogen, silane, hydrazine, magnesium, etc.) flames.
Third-party performance certified to detect saturating signal source in 15 milliseconds, 1 square foot gasoline flame at 50 feet in 1 second typical. Horizontal field of view 120°.
Environmental ratings
Rated:
Class I, Division 1, Groups B, C, D (explosion proof ) Class II, Division 1, Groups E, F, G (dust ignition proof) NEMA Type 4X weatherproof, dust-tight, watertight CE0081 II 2 G/D
Ex db IIB + H2 T5 Gb for gas on 660-0XXXX
Ex tb IIIC T100°C Db IP66 for dust on 660-0XXXX
Ex db IIB + H2 T4 Gb for gas on 660-1XXXX
Ex tb IIIC T135°C Db IP66 for dust on 660-1XXXX
Housings
Copper-free aluminum conversion coated to MIL-C-5541C, Class 3 (white) Stainless Steel 316 housing with passive finish per MIL-S-5002C, Type 1
Operating temperature
Standard operating temperature range: -40Co to +85o C (-40oF to 185oF)
Special high temperature version:
-40Co to +125oC (-40Fo to 257oF)
Operating humidity
0-95% RH (non-condensing)
(withstands up to 100% RH for short periods)
View more about Omniguard Flame and Gas Detector 660-10100 on main site